🔧 Input Parameters
📐 Power Triangle
Real Power (P)
996.2 W
Reactive Power (Q)
575.0 VAR
Apparent Power (S)
1150.0 VA
Power Factor
0.866
〰️ Voltage & Current Waveform — Phase Angle (φ) & Power Delivered
The graph below plots voltage (red) and current (blue) over time. The horizontal shift between the two waves is the phase angle φ. Yellow shaded regions show where the instantaneous product V(t)·I(t) is positive — i.e. where power is actually delivered to the load. At lagging φ > 0 current peaks after voltage (inductive); at leading φ < 0 current peaks before voltage (capacitive); at φ = 0 the two are in phase and all energy is delivered (purely resistive).
📘 AC Power Formulas
P = S × cos(φ)
P = S² − Q² (squared)
Q = S × sin(φ)
Q = √(S² − P²)
S = P / cos(φ)
S = √(P² + Q²)
PF = P / S
PF = R / Z
📊 Step-by-Step Calculation
AC Power Calculator: The Complete Guide to Real (W), Reactive (VAR) & Apparent (VA) Power
This AC power calculator (also called an AC wattage calculator) instantly computes real power (watts), reactive power (VAR), apparent power (VA), and power factor from RMS voltage, RMS current, and the phase angle between them. It draws a live power triangle and a voltage–current waveform with the phase angle marked, then shows the full step-by-step working. Use it for electrical design, motor and transformer sizing, power factor correction, utility billing analysis, and homework on AC circuits.
Quick Answer: The Three AC Power Formulas
| Quantity | Formula | Unit | Example (230 V, 5 A, 30°) |
|---|---|---|---|
| Apparent Power (S) | S = V × I | VA (volt-amperes) | 230 × 5 = 1150 VA |
| Real Power (P) | P = V × I × cos(φ) | W (watts) | 1150 × 0.866 ≈ 996 W |
| Reactive Power (Q) | Q = V × I × sin(φ) | VAR | 1150 × 0.5 = 575 VAR |
| Power Factor (PF) | PF = cos(φ) = P / S | dimensionless | cos 30° = 0.866 |
What Is AC Power?
In an AC (alternating current) circuit the voltage and current are sinusoidal: they swing positive and negative many times per second (50 or 60 Hz on most grids). Whenever the load contains inductance or capacitance, the current is shifted in time relative to the voltage — they are out of phase. Because power at each instant is the product V(t) × I(t), this phase shift causes part of the energy to flow back and forth between source and load without ever being consumed. AC power therefore splits into three separate quantities that must be calculated and tracked separately.
The Three Types of AC Power
Real (Active) Power — P, in watts (W)
Real power is the average power that actually does useful work: heat, light, mechanical rotation, sound. This is what your electricity meter records and what you pay for.
V and I are RMS values, φ is the phase angle between them, and cos(φ) is the power factor.
Reactive Power — Q, in volt-amperes reactive (VAR)
Reactive power oscillates between the source and the load's reactive elements (inductors and capacitors) without doing net work. Inductors absorb reactive power to build magnetic fields; capacitors generate it by storing energy in an electric field. Although reactive power does no useful work, it must be supplied so motors and transformers can operate.
Q is positive for inductive (lagging) loads and negative for capacitive (leading) loads.
Apparent Power — S, in volt-amperes (VA)
Apparent power is the magnitude of the complex power vector — simply the product of RMS voltage and RMS current. It determines how much current the source, conductors, and transformer must carry. Generators, transformers, and UPS systems are always rated in kVA (apparent power), never in kW.
S = √(P² + Q²)
S is always ≥ P. The unit is VA, distinct from W, to emphasize that not all of it does work.
The Power Triangle
The relationship between real, reactive, and apparent power is a right triangle (shown in the live diagram above):
• Horizontal side (adjacent) = P (real power, W)
• Vertical side (opposite) = Q (reactive power, VAR)
• Hypotenuse = S (apparent power, VA)
• Angle between P and S = φ (phase angle)
• cos(φ) = P/S = Power Factor
The Phase Angle (φ) and the V–I Waveform
The phase angle φ is the time shift between the voltage and current waveforms, expressed in degrees of one cycle. In the live waveform diagram above the two sinusoids show this offset directly. When V and I have the same sign at the same instant the instantaneous power V·I is positive — energy flows from source to load. When they have opposite signs, V·I is negative and energy briefly flows back to the source. The yellow shaded regions mark the intervals where net power is delivered; as the phase angle grows, those regions shrink, which is exactly why real power drops as cos(φ) when the load becomes reactive.
- φ = 0°: V and I peak together. All of V × I is positive; power delivered = V × I (purely resistive, PF = 1).
- φ = 30° (lagging): Current peaks slightly after voltage; some intervals have V·I < 0. Real power drops to V × I × cos 30° ≈ 0.866 × V × I.
- φ = 60°: Larger shift, only V × I × cos 60° = 0.5 × V × I of useful power delivered. Heavy reactive component.
- φ = 90°: Pure inductor or capacitor — no net real power delivered at all; all energy sloshes back and forth.
Understanding Power Factor
Power factor measures how efficiently the load converts apparent power into useful real power:
• PF = 1.00 → purely resistive — all apparent power becomes real power
• PF = 0.95 → typical well-corrected industrial site
• PF = 0.80 → 80% useful, 20% reactive — utilities may charge a penalty
• PF = 0.50 → only half the apparent power does useful work — very inefficient
• PF = 0.00 → purely reactive — no real power, only circulating reactive current
Leading vs Lagging Power Factor
- Lagging (φ > 0, inductive): Current lags voltage. Caused by motors, transformers, solenoids, fluorescent ballasts. The vast majority of industrial loads are lagging.
- Leading (φ < 0, capacitive): Current leads voltage. Caused by capacitor banks, lightly loaded long underground cables, some switched-mode supplies.
- Unity (φ = 0, resistive): Voltage and current in phase. Heaters, incandescent lamps, resistive loads.
kVA ↔ kW ↔ kVAR Conversions
| Conversion | Formula | Example |
|---|---|---|
| kVA to kW | kW = kVA × PF | 10 kVA × 0.9 = 9 kW |
| kW to kVA | kVA = kW ÷ PF | 9 kW ÷ 0.9 = 10 kVA |
| Amps from kW (1-phase) | I = (kW × 1000) ÷ (V × PF) | 9000 ÷ (230 × 0.9) ≈ 43.5 A |
| Amps from kVA (1-phase) | I = (kVA × 1000) ÷ V | 10 000 ÷ 230 ≈ 43.5 A |
| kVAR from kW & PF | kVAR = kW × tan(arccos PF) | 9 × tan(25.8°) ≈ 4.36 kVAR |
Worked Examples
Example 1: Motor Load Analysis
Problem: A 230 V, 50 Hz supply drives a single-phase motor drawing 10 A at PF = 0.85 lagging.
φ = cos⁻¹(0.85) = 31.79°
S = 230 × 10 = 2,300 VA
P = 2,300 × 0.85 = 1,955 W
Q = 2,300 × sin(31.79°) = 1,212 VAR
Check: √(1955² + 1212²) ≈ 2,300 VA ✓
Example 2: Power Factor Correction Savings
Problem: A factory draws 50 kW at PF = 0.70. How much apparent power does the utility supply, and what happens if PF is corrected to 0.95?
Before: S = P / PF = 50 / 0.7 = 71.43 kVA, Q = √(S² − P²) = 50.97 kVAR
After: S = 50 / 0.95 = 52.63 kVA — utility supplies 26 % less current.
The factory's real power consumption (50 kW) is unchanged, but line losses and cable heating drop significantly.
Example 3: Sizing a Generator
Problem: A standby generator must supply a 40 kW load at PF = 0.8 lagging. What kVA rating is needed?
kVA = kW / PF = 40 / 0.8 = 50 kVA
The generator must be rated 50 kVA even though only 40 kW of useful work will be done — its windings have to carry the full current associated with 50 kVA.
Single-Phase vs Three-Phase AC Power
For single-phase systems use the formulas above. For balanced three-phase systems multiply by √3 (≈ 1.732):
S = √3 × VLL × I (in VA)
P = √3 × VLL × I × cos(φ) (in W)
Q = √3 × VLL × I × sin(φ) (in VAR)
Practical Applications
- Electricity billing & PF penalties: Utilities meter real power (kWh) but commercial customers often pay a penalty when PF falls below 0.9.
- Transformer & generator sizing: These are rated in kVA because their windings must handle the total current, not only the in-phase component.
- Power factor correction (PFC): Adding capacitor banks supplies reactive power locally, reducing utility current draw and saving on bills.
- Cable and breaker sizing: Sized for I = S / V (not P / V), so low PF demands thicker conductors and larger breakers.
- UPS & inverter ratings: Spec'd in VA — pay attention to PF if your load is reactive.
- Motor commissioning: Comparing measured PF with nameplate value reveals underloaded or oversized motors.
- Solar & renewable interconnection: Grid codes typically require inverters to operate at or near unity PF and may demand VAR support during faults.
Common AC Voltages and Their Use
| Voltage | Frequency | Region / Use |
|---|---|---|
| 120 V | 60 Hz | North America residential |
| 230 V | 50 Hz | EU / UK / India / Asia residential |
| 208 V / 240 V | 60 Hz | North America split-phase / light commercial |
| 400 V (3-phase L-L) | 50 Hz | EU industrial |
| 480 V (3-phase L-L) | 60 Hz | US industrial |
Typical Power Factors of Common Loads
- Incandescent lamps / heaters: ~1.0 (purely resistive)
- Modern LED lighting (good drivers): 0.90 – 0.99
- Fluorescent lamps (electronic ballast): 0.85 – 0.95
- Induction motors (fully loaded): 0.80 – 0.90 lagging
- Induction motors (lightly loaded): 0.40 – 0.70 lagging — surprisingly poor
- Welders / arc furnaces: 0.30 – 0.70 lagging
- Switched-mode PSUs (no PFC): ~0.6, with non-sinusoidal current
- Switched-mode PSUs (with active PFC): > 0.95
Frequently Asked Questions
Why can't I just use P = V × I for AC?
Because in AC circuits, voltage and current may be out of phase. P = V × I gives apparent power (in VA), not real power (in W). The correct formula for real power is P = V × I × cos(φ).
How do I convert kVA to kW?
Multiply by the power factor: kW = kVA × PF. For example, 10 kVA at PF 0.9 equals 9 kW.
How do I convert kW to kVA?
Divide by the power factor: kVA = kW ÷ PF. For example, 9 kW at PF 0.9 equals 10 kVA.
How many amps is 1 kW at 230 V?
It depends on the power factor. At unity PF: I = 1000 ÷ 230 ≈ 4.35 A. At 0.8 PF: I = 1000 ÷ (230 × 0.8) ≈ 5.43 A.
What is a good power factor?
Above 0.95 is excellent. 0.85–0.95 is acceptable for most industrial sites. Below 0.85 typically triggers utility penalty charges and increases line losses.
How do I improve a poor power factor?
Add power factor correction capacitors in parallel with inductive loads. Capacitors supply reactive power locally, so the utility only has to supply real current. Automatic PFC panels switch capacitor stages in and out as the load changes.
What is the difference between leading and lagging?
Lagging means the current lags the voltage (inductive load); leading means current leads voltage (capacitive load). Most real-world loads are lagging.
Does the power triangle work for non-sinusoidal currents?
The classic power triangle (S² = P² + Q²) assumes pure sinusoids. With distorted (harmonic-rich) currents, you also need to include distortion power D, giving S² = P² + Q² + D². This is common with switched-mode loads.
Related Electrical Calculators
- DC Power Calculator — P = V × I and the 12-formula power wheel
- Ohm's Law Calculator — V = I × R fundamentals
- Inductor Calculator — inductive reactance XL
- Capacitor Calculator — capacitive reactance XC
- RLC Parallel Resonance — impedance, admittance, Q-factor
- RLC Series Resonance